The air conditioner power calculator determines the cooling capacity needed to cool a room and the heating capacity needed to heat it. The calculation takes into account room dimensions, external walls, insulation, glazing, temperature conditions and other factors that affect thermal load.
For cooling, an area-based calculation is used with successive adjustments for room conditions. For heating, heat losses through the building envelope and air exchange are calculated. The results are expressed in kW and BTU/h, allowing you to estimate the required capacity of an air conditioner or split system.
Room area. Floor area A in m2 is calculated from length L and width B in metres. Multiplying the area by ceiling height H gives room volume V in m3.
A = L × B
V = A × H
External walls. Only walls adjoining outdoor air are included. Their total length Pext is determined from the selected sides of a rectangular room. With four external walls, the full perimeter is used.
Pext = 2 × (L + B)
The gross area of external walls before subtracting openings is calculated by multiplying their total length by the room height.
Aext = Pext × H
If there are no external walls, their area is taken as zero. In that case, windows and an external door do not contribute to the thermal load. For a square room, all sides have the same length, so the number of external walls is sufficient.
Base cooling capacity. For preliminary selection of a residential air conditioner, a guideline of 100 W per 1 m2 of floor area is often used. This is the starting value, subsequently adjusted for the actual conditions.
Qbase = 100 × A
For example, a 20 m2 room has a base capacity of 2000 W, or 2 kW.
Height adjustment. The reference ceiling height is 2.4 m. At other heights, base capacity changes in proportion to the ratio of actual to reference height.
Qheight = Qbase × H / 2.4
At a height of 3 m, the factor is 1.25, so base capacity increases by 25%. This relationship is a simplified way to account for room volume.
Temperature difference. The desired indoor temperature is subtracted from the outdoor temperature. If outdoor air is cooler than indoor air, a difference of 0°C is used for this adjustment.
ΔT = max(0, Tout - Tin)
Temperature factor. The reference temperature difference is 8°C, for which the factor is 1.00. For each degree of deviation, the calculated capacity changes by 2.5%.
kT = 1 + 0.025 × (ΔT - 8)
The factor is limited to the range 0.85 to 1.20. For a temperature difference of 2°C or less it is 0.85, at 8°C it is 1.00, and at 16°C or more it is 1.20.
After adjusting for height and temperature conditions, a reference cooling capacity is obtained. The remaining adjustments are calculated relative to it.
Qref = Qbase × H / 2.4 × kT
External wall fraction. The external wall area is compared with the combined area of all four room walls. The resulting fraction f indicates how much of the vertical building envelope faces outdoor air.
f = Aext / (2 × (L + B) × H)
A 50% external wall fraction is the reference case. The exposure adjustment is 20% of reference capacity per unit change in this fraction. For example, a 100% fraction increases capacity by 10%, while having no external walls reduces it by 10%.
Qexposure = Qref × 0.20 × (f - 0.50)
Wall insulation. An additional factor depends on the insulation quality of external walls:
The adjustment is scaled to the external wall fraction. At 50%, the full factor applies. At 100%, its effect is doubled. The multiplier is capped at 2.
Qins = Qref × kins × min(f / 0.50, 2)
The total external wall adjustment is the sum of the effects of wall exposure and insulation.
Qwalls = Qexposure + Qins
Glazing ratio. Window area is compared with floor area. The reference glazing ratio is 15%, for which the separate glazing adjustment is zero.
r = Awin / A
kwin = 0.08 × (r - 0.15) / 0.15
The factor is limited to -0.08 to +0.12. With no windows, the adjustment is -8%. At 15% glazing it is zero, and at 30% it is +8%. At a glazing ratio of 37.5% or higher, the maximum adjustment of +12% applies.
Qwin = Qref × kwin
Sun exposure. An additional adjustment accounts for the intensity of sunlight reaching the windows:
The solar factor is multiplied by the ratio of the actual glazing fraction to the reference 15%. This multiplier is capped at 2, and the final solar adjustment is limited to -10% to +20% of reference capacity.
ksolar = ksun × min(r / 0.15, 2)
Qsolar = Qref × ksolar
If there are no external walls or windows, the solar adjustment is zero. Negative factors represent a reduction in calculated load relative to the reference conditions, not physical cooling of the room by sunlight.
Roof and attic. For rooms directly beneath a roof, an additional adjustment is applied according to the insulation of the upper structure:
Qroof = Qref × kroof
Heat gains from occupants. The base model assumes normal occupancy of up to two people. From the third person onward, 180 W is added per additional person. With zero, one or two people, this adjustment is zero.
Qpeople = max(0, N - 2) × 180
Household appliances. The electrical power of appliances operating simultaneously is added directly to the heat load in watts. For example, appliances drawing 300 W increase the calculated cooling requirement by 300 W. The assumption is that almost all the stated electrical energy becomes heat inside the room.
Qequipment = Pequipment
Total cooling capacity. The reference capacity is added to all positive and negative adjustments. The result cannot be lower than zero.
Qcool = max(0, Qref + Qwalls + Qwin + Qsolar + Qroof + Qpeople + Qequipment)
Conversion to BTU/h. Calculated power in watts is multiplied by 3.41214. To obtain kilowatts, watts are divided by 1000.
QBTU = Qcool × 3.41214
QkW = Qcool / 1000
Capacity class selection. The smallest value not lower than the calculated requirement is selected from the nominal range of 7000, 9000, 12000, 15000, 18000, 21000, 24000, 28000, 30000, 36000, 42000, 48000 and 60000 BTU/h. Above 60000 BTU/h, the value is rounded up to the next 1000 BTU/h.
The reserve percentage is calculated as the ratio of the selected capacity class to the calculated requirement.
Reserve = (Qsize / QBTU - 1) × 100%
The BTU/h capacity class is a guideline. The actual rated cooling capacity of a particular air conditioner may differ from the kW value obtained by directly converting BTU to kW. When selecting equipment, compare the calculated load with the model's specifications.
Design temperature difference. To determine the air conditioner capacity required for heating, the difference between the specified indoor temperature and the outdoor winter temperature is used.
ΔT = max(0, Tin - Tout)
For example, at +20°C indoors and -15°C outdoors, the difference is 35 K. If the outdoor temperature is not lower than the indoor temperature, the calculated difference is zero.
Heat transfer through building elements. Heat loss is calculated as the product of the element's area, its thermal transmittance U and the temperature difference.
Q = U × A × ΔT
Here, Q is heat loss in watts, A is the area in m2, and U is thermal transmittance in W/(m2·K). The lower the U-value, the better the insulation and the lower the heat loss.
Wall insulation. Instead of calculating every layer of a wall, approximate thermal transmittance values are used:
Net wall area. Window and external door areas are subtracted from the gross external wall area. This prevents heat loss through the same part of the envelope from being counted twice.
Awall = Aext - Awin - Adoor
Qwall = Awall × Uwall × ΔT
If the combined window and door area exceeds the external wall area, the calculation is not performed until the input values are corrected.
Heat loss through windows. The following approximate thermal transmittance values are used for glazing:
Qwin = Awin × Uwin × ΔT
External door. Typical areas and thermal transmittance values are assumed for different constructions:
Qdoor = Adoor × Udoor × ΔT
If there is no external door, its area and heat loss are zero.
Heat loss through the ceiling. The full floor area is used for the upper structure. The factor depends on what lies above the room:
Qceiling = A × Uceiling × ΔT
Heat loss through the floor. The following factors are used for the lower boundary of the room:
Qfloor = A × Ufloor × ΔT
The same indoor-outdoor temperature difference is applied to both the ceiling and floor. These are simplified effective values. Attic, basement and ground temperatures are not calculated separately.
Ventilation heat loss. When cold outside air enters a room, heat is required to raise its temperature to the indoor level. The heat loss depends on room volume, air-change rate and temperature difference.
Qair = 0.34 × n × V × ΔT
The factor 0.34 represents the approximate volumetric heat capacity of air. The air-change rate n is expressed in h-1 and indicates how many room volumes of air are replaced by outside air each hour.
The following values are used for an approximate calculation:
For ordinary living spaces, an air-change rate of around 0.5 h-1 is often used for preliminary estimates. Increasing air exchange increases the associated heat losses proportionally.
Total heat loss. Heat losses through the external walls, windows, door, ceiling, floor and air exchange are added together. The result represents the heating capacity needed to offset these losses at the specified temperatures.
Qheat = Qwall + Qwin + Qdoor + Qceiling + Qfloor + Qair
The total capacity is shown in watts and kilowatts. The same conversion factor of 3.41214 is used for BTU/h.
QkW = Qheat / 1000
QBTU = Qheat × 3.41214
Specific thermal load. For both modes, capacity is also calculated per unit of floor area and room volume.
qA = Q / A
qV = Q / V
The first value is expressed in W/m2, the second in W/m3. These figures help compare thermal loads in rooms of different sizes.
Choosing an air conditioner for heating. The calculated heating capacity must be compared with the performance of the actual equipment at the chosen outdoor temperature. With heat-pump air conditioners, available heating capacity may decrease as outdoor temperatures fall. Rated capacity alone is therefore insufficient.
EN ISO 52016-1 "Energy performance of buildings. Energy needs for heating and cooling, internal temperatures and sensible and latent heat loads. Part 1: Calculation procedures". This standard describes methods for estimating buildings' heating and cooling energy needs and thermal loads. The calculator uses a simplified steady-state model with fixed factors, not a full calculation to this standard.
EN 12831-1 "Energy performance of buildings. Method for calculation of the design heat load. Part 1: Space heating load". This standard establishes methods to determine the required heating capacity from transmission and ventilation heat losses. These components are used in simplified form for the heating mode.
EN ISO 6946 "Building components and building elements. Thermal resistance and thermal transmittance. Calculation methods". This standard explains how to calculate thermal resistance and thermal transmittance of building structures. The calculator uses approximate preset values instead of a layer-by-layer calculation.
EN 14511-2 "Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors. Part 2: Test conditions". This standard specifies the test conditions for equipment, including determining cooling and heating capacities. When choosing an air conditioner, check the manufacturer's performance figures for the relevant temperature conditions.
Cooling calculations estimate heat gains from floor area, sunlight, glazing, occupants and appliances. Heating calculations determine the capacity needed to compensate for heat losses through building elements and air exchange. The same room can therefore have substantially different results.
An area-based estimate of 100 W/m2 is suitable for preliminary cooling capacity estimates under ordinary conditions. However, rooms with the same area can have different thermal loads due to ceiling height, glazing, insulation and sun exposure. For heating, building heat loss and the design outdoor winter temperature are particularly important.
For cooling, choose a representative high outdoor temperature at which the air conditioner must maintain the desired indoor temperature. For heating, use your region's design winter temperature rather than the seasonal average. A larger temperature difference increases the calculated thermal load, although the cooling temperature adjustment is limited to its specified range.
An air conditioner's rated heating capacity and its actual output at low outdoor temperatures can differ considerably. Two units in the same BTU capacity class may provide different heating outputs in freezing weather. Therefore, the calculated heating requirement is displayed separately, and the model should be chosen according to its stated heating output at the required winter temperature.
For cooling, the insulation level adjusts the calculated load through percentage corrections related to external wall exposure. For heating, thermal transmittance values directly determine heat loss through walls, windows, the ceiling and the floor. For example, reducing external wall transmittance from 1.30 to 0.25 W/(m2·K) reduces the calculated heat loss through its opaque area by about 81% at the same area and temperature difference.